| Model |
XJ11 (XJ3-D) |
| Protection function |
1.over voltage protection, 2.under voltage protection ,
3. phase failure protection, 4.phase sequence protection |
| Operation power |
3-phase AC380v, 50Hz/60 Hz |
| The range of voltage protection |
Under voltage protection: 300-380v |
| Over voltage protection: 380-460v |
| Delay time range |
actuating time of Under voltage protection: 2-9s |
| actuating time of Over voltage protection:1.5-4s |
| actuating time of phase failure and phase sequence protection:2s/Max. |
| Reset |
Automatically reset |
| Contact capacity |
3A AC380 v (resistance) |
| Power consumption |
≤1w |
| Insulation resistance |
≥100MΩ (20°C relative humidity 85%) |
| Contact resistance |
≤0.03Ω |
| Electrical life |
1×105 times |
| Ambient temperature |
-5°C~+40°C |
| Ambient humidity |
85%(20±5°C) |
| Dielectric strength |
No breakdown and flashover, under the condition of lasting to operate power AC(50Hz)1500V for 1 minute. |
| Installation type |
1. 35mm track mounting, 2. screw mounting on the back board |